Project Description

CJX2N(NLC1-D) ac contactor

Introduction

AC contactor is widely used in power transmission system. Applicable to long-distance frequent switching on and switching end DC main circuit and large capacity control circuit in, it main control object is all motor, and can also be used for electric welder control, capacitor banks, and the electric heating device, lighting equipment and other loads. For example, power industry, industrial and mining enterprises, iron and steel plants, and some large power will use it. Can also cooperate with the fuse, the dynamic air circuit breaker, thermal relay and other electrical use, in order to better protect the line current.

An air conditioning unit is a complex system of electronic components that must work together so that your AC system can run at the right times.

Why do we need to use AC contactor?

We live around a lot of large equipment to start the knife gate will have a spark, arc, will have a security risk, if it is safe to contact the remote control is much more safe.

AC contactor is widely used in power transmission system. Applicable to long-distance frequent switching on and switching end DC main circuit and large capacity control circuit in, it main control object is all motor, and can also be used for electric welder control, capacitor banks, and the electric heating device, lighting equipment and other loads. For example, power industry, industrial and mining enterprises, iron and steel plants, and some large power will use it. Can also cooperate with the fuse, the dynamic air circuit breaker, thermal relay and other electrical use, in order to better protect the line current.

Its advantages: it has a large number of control, the action is rapid, safe and easy operation, etc., and has the function of under voltage release, the application is very extensive in industrial and agricultural production. Simple wiring. The contact point of the AC contactor is made of silver tungsten alloy, which has good electrical conductivity and high temperature resistance. Can prolong the service life of the switch, protect the electric equipment.

type NLC1-D09 NLC1-D12 NLC1-D18 NLC1-D25 NLC1-D32
Rated working current(A) AC3 9 12 18 25 32
AC4 3.5 5 7.7 8.5 12
Ac3 capacity of phase 3
squirrel-cage motor AC3(KW)
220/230V 2.2 3 4 5.5 7.5
380/400V 4 5.5 7.5 11 15
415V 4 5.5 9 11 15
440V 4 5.5 9 11 15
500V 5.5 7.5 10 15 18.5
660/690V 5.5 7.5 10 15 18.5
Rated heat current(A) 20 20 32 40 50
Electrical life AC4X10^4 20 20–5 20–7 15–7 15–7
AC4X10^6 2 2 2 2 2
Mechanical 20 20 20 20 20
Number of the contact 3P+NO 3P+NC+NO
3P+NC
type NLC1-D40 NLC1-D50 NLC1-D65 NLC1-D80 NLC1-D95
Rated working current(A) AC3 40 50 65 80 95
AC4 18.5 24 28 37 44
Ac3 capacity of phase 3
squirrel-cage motor AC3(KW)
220/230V 11 15 18.5 22 25
380/400V 18.5 22 30 37 45
415V 22 25 37 45 45
440V 22 30 37 45 45
500V 22 30 37 55 55
660/690V 30 33 37 45 45
Rated heat current(A) 60 80 80 125 125
Electrical life AC4X10^4 10–7 7 7–6 7–5 7–5
AC4X10^6 2 2 1.6 1.6 1.6
Mechanical 20 20 20 10 10
Number of the contact 3P+NC+NO

Standard control circuit voltages

volts(VAC) 24 42 48 110 220/
230
230 240 380/
400
400 415 440 500 660
50Hz B5 D5 E5 F5 M5 P5 U5 Q5 V5 N5 R5 S5 Y5
60Hz B6 D6 E6 F6 M6 U6 Q6 R6
50/60Hz B7 D7 E7 F7 M7 P7 U7 Q7 V7 N7 R7